Description
AES 916 G/C
Maximum active electric power(kW): 9405
Crankshaft rotation frequency, r/min/ 750
Crankshaft rotation frequency, rpm
Mean effective pressure, bar/ Average effective pressure, bar 20
Voltage(V): 6300
Thermal capacity of the cooling system and cooled exhaust gases(kW):8550+/-8%
Fuel energy(kW): 19585 +5%
Gas consumption with a heat of combustion of 10 kWh/nm3
Electric efficiency(%): 48,0
Thermal efficiency(%): 43,7
Total Efficiency(%): 91,7
Generator effiency(%): 97.8
The cogeneration unit shall comply with the following minimum requirements:
Thermal efficiency: ≥ 35.0%
Electrical efficiency: ≥ 35.0%
Overall efficiency: ≥ 85.0%
NOx emissions (at 15% O₂): ≤ 500 mg/Nm³ (dry gas)
CO emissions (at 15% O₂): ≤ 250 mg/Nm³ (dry gas)
If the current configuration of the cogeneration unit does not comply with the applicable emission limits, the installation of an additional catalytic emissions control system shall be mandatory in order to reduce emissions to the permissible levels.