Description
Gas engine genset(s) 1 x TCG 2020 V12:
Combustion gas Natural gas
Methane number 80
Lower heat value kWh/Nm³ 10.18
Gas density kg/Nm³ 0.79
Electrical terminal power at cos φ = 1.000 /
ind./overexcited
kW 1200
Cooling water heat (± 8%) kW 609
NT mixture cooler heat (± 8%) kW 107
Exhaust gas recooling temperature °C 120
Exhaust gas heat at recooling temperature (± 8%) kW 580
Fuel use (+ 5%) kW 2749
Electrical efficiency % 43.7
Thermal efficiency % 43.3
Total efficiency % 87.0
The cogeneration unit shall comply with the following minimum requirements:
Thermal efficiency: ≥ 35.0%
Electrical efficiency: ≥ 35.0%
Overall efficiency: ≥ 85.0%
NOx emissions (at 15% O₂): ≤ 500 mg/Nm³ (dry gas)
CO emissions (at 15% O₂): ≤ 250 mg/Nm³ (dry gas)
If the current configuration of the cogeneration unit does not comply with the applicable emission limits, the installation of an additional catalytic emissions control system shall be mandatory in order to reduce emissions to the permissible levels.